400-627-1108Mobile station
|Chinese|English

Product

Current Position:Home > Product > Transformer tester

Product details

TKRZSweep Frequency Response Analyzer(FRA Test Set)

Other name:Electric power transformer winding deformation test instrument

Specification Certificate of identification Service promise

Current limiting protection Power amplifier protection Voltage short circuit protection Open circuit protection Thermal protection of power amplifier

Note:Regarding product purchase, technical maintenance and other services, welcome to send email:

IntroductionParametersAccessoriesService

Product Introduction

Transformer winding deformation test instrument based on the measurement of the characteristic parameters of transformer internal winding the internal fault frequency response analysis (FRA) method which is being developed in developed countries is adopted to make an accurate judgment of transformer internal fault.

After the design and manufacture of transformer is completed the line coil and internal structure are determined. Therefore for a multi-winding transformer line coil if the voltage grade is the same and the winding method is the same the corresponding parameters (Ci Li) of each line coil should be determined. Therefore the frequency domain characteristic response of each line coil is determined accordingly and the frequency spectrum of the corresponding three-phase line coil is comparable to some extent.

The distribution parameters of transformer windings will change when short-circuit between turns and phases occurs in the test process or collision occurs in the transportation process resulting in the relative displacement of the line coil and the deformation of the line coil caused by electromagnetic tension in the short-circuit and fault state during the operation process. Then it influences and changes the original frequency domain characteristics of the transformer that is amplitude change of frequency response and resonance frequency offset. The transformer winding test instrument developed according to the response analysis method is such a novel non-destructive testing equipment for transformer internal faults. It is suitable for the internal structure fault detection of 63kV ~ 500kV power transformer.

product names:Electric power transformer winding deformation test instrument、Transformer winding deformation detector、Transformer winding deformation meter、Transformer winding deformation analyzer


Product Characteristics

 
  • 1、Transformer winding deformation test instrument acquisition and control adopt high speed and high integration microprocessor.

  • 2、USB interface for laptop with instrument communication

  • 3、No line bluetooth interface between laptop and instrument

  • 4、The hardware movement adopts DDS special digital high-speed frequency sweeping technology (USA). Through the test the faults of winding distortion bulge shift tilt short-circuit deformation between turns and pick up short-circuit between phases can be accurately diagnosed

  • 5、High-resolution dB value measurement dual-channel 16-bit A/D

  • 6、 The signal output amplitude can be adjusted by software to a maximum peak of 10V

  • 7、The computer generates an electronic document of the results(Word)

  • 8、Select precise and highly stable components repeat the test on the same phase and measure the repetition rate above 99.5%

  • 9、Finished circuit board surface is specially treated resistant to water and harmful gas pollution

  • 10、The Transformer winding deformation test instrument produced by our company has the functions of linear sweep frequency measurement and piecewise sweep frequency measurement and is compatible with the measuring modes of the current two domestic technical schools

  • 11、The amplitude-frequency characteristic conforms to the national technical index of amplitude-frequency characteristic test instrument. The abscissa (frequency) has two kinds of line-like indexing and logarithmic indexing so the printed song line can be either line-like or logarithmic indexing line which can be selected by the user according to the actual situation

  •  

Product Parameters

scanning way:(The instrument has a linear sweep measurement system and a segmented sweep measurement system )

Linear sweep distribution Sweep measuring range (1kHz)~(2MHz)
Sectional sweep measurement distribution Sweep measuring range (0.5kHz)~(1MHz)
(0.5kHz)~(10kHz)
(10kHz)~(100kHz)
(100kHz)~(500kHz)
(500kHz)~(1000kHz)
Range of amplitude (-100dB)~(+20dB)
Accuracy of amplitude measurement ±1dB
Sweep accuray 0.01%
signal input impedance 1MΩ
signal output impedance 50Ω
In phase test repetition rate 99.5%
Dimensions 300×340×120mm3
Dimensions of Aluminum Alloy Packaging

Box

310×400×330mm3
Weight 10kg

Quality Keep Improving - Service Pursuing Perfection Pre-sales service commitment Provide professional consulting service; dedicated salesman and professional technical engineer to answer customer questions Ensure customer get the detailed information about the product in hand Reasonable price. Quotation stamped and confirmed by Manager

Welcome customers visit on-purchase service commitment The contract and the technical agreement to sign by both parties Being trustworthy, follow the requirements and ensure successful implementation of signed contracts and technical agreements Focus on communication, actively communicate with users, take notes of user’s questions and schedule, provide the necessary technical support. Move quick and efficient, professional on delivery, installation, debugging, training and others

After-sales service commitment Professional after-sales service department; ask and listen to customer’s feedback about the products and take records. Product guaranty: one year free warranty, life long maintenance, since the delivery of the product Provide solutions within 24 hours when there is problems feedback from customer. Professional research and development team.

Recommended products

Email:
whgdmk@yeah.net
Skype:
Emma Lei
live:.cid.d703d549beaabb3e
电话:
+8618164248846