TKHG-QCurrent Transformer Field Calibrator

Other name:Current Transformer Field Calibrator

Specification Certificate of identification Service promise

Current limiting protection Power amplifier protection Voltage short circuit protection Open circuit protection Thermal protection of power amplifier

Note:Regarding product purchase, technical maintenance and other services, welcome to send email:

IntroductionParametersAccessoriesService
The high-voltage electric energy measurement devices of power plants and substations and the electric energy measurement devices of a large number of users are related to the interests of power generation power transmission power supply and multiple parties of users. In order to ensure accurate measurement the inspection must be carried out in accordance with SD109 "Inspection Regulations for Electric Energy Measurement Devices" and DL / T448-2000 "Technical Management Regulations for Electricity Measurement Devices".
 
TKHG-Q  current transformer field calibrator was developed based on high-end testing technology large-scale electronic circuit design and in compliance with relevant national regulations. It solves the problems of on-site verification of current transformer and voltage transformer with high working intensity and tedious operation. At the same time the product has reliable performance and powerful functions.



1. The instrument also has a recursive method to measure the current transformer error which is convenient for the on-site verification of the measurement device.
 
2. On-site verification of current transformers does not require standard current transformers current risers load boxes voltage control boxes and high-current conductors. It uses extremely simple test wiring and operations to achieve the verification of current transformers greatly reducing the work The intensity and working efficiency are improved which is convenient for the on-site verification of transformers.
 
3. The instrument has a standard voltage transformer equivalent to the same transformation ratio of the measured current transformer. Its accuracy can reach 0.05 level and the transformation ratio and no-load error of the measured current transformer can be accurately measured. Then combine the test results of impedance and admittance to calculate the error of the transformer.
 
4. Adopt different frequency power supply test close to power frequency to prevent on-site power frequency electromagnetic radiation and series interference.
 
5. Wide measuring range can reach 5A / 5A ~ 25000A / 5A or 5A / 1A ~ 6300A / 1A.
 
6. With the function of current transformer transformation ratio and secondary winding internal resistance test.
 
7. Adopt 800 × 600 high-resolution large-screen color liquid crystal display with humanized interface and operation design and use the touch screen to assist the operation making the operation more convenient and fast.
 
8. Using precise software algorithms the accuracy of measurement data is further improved.
 
9. It has the intelligence to judge the external wiring status and prompts the wiring error transformation ratio polarity error etc.
 
10. Automatically round the test data and judge whether it is out of tolerance. The out-of-tolerance data is displayed in orange and the out-of-tolerance is displayed at the lower right corner of the window.
 
11. Directly issue on-site verification conclusions qualified or out of tolerance.
 
12. Large-scale memory can store up to 1000 field test data.
 
13. Use RS232 or USB interface to connect computer to print data certificate.
 
14. The engineering plastic mold chassis is used to prevent shock and pressure to ensure the safety of on-site operators and equipment.


 

1. Current transformer error measurement section
 
1) Overall accuracy: 1/3 of the error limit of the measured current transformer
 
2) Test range: 5A / 5A ~ 25000A / 5A or 5A / 1A ~ 6300A / 1A

Transformer rated primary current range with secondary current of 5A

5

7.5

10

15

20

25

30

40

50

60

75

80

100

120

150

160

200

250

300

315

400

500

600

630

750

800

1000

1200

1250

1500

1600

2000

2500

3000

3150

3200

4000

5000

6000

6300

 

Transformer rated primary current range with secondary current 1A

5

7.5

10

15

20

25

30

40

50

60

75

80

100

120

150

160

200

250

300

315

400

500

600

630

750

800

1000

1200

1250

1500

1600

2000

2500

3000

3150

3200

4000

5000

6000


6300

 

Note: The current transformer with a secondary current of 1A can be converted to 31500A / 1A by the method of equal-ampere turns measurement. Other test methods for the current transformer ratios that do not appear in the table are as follows:
 
Use the equal ampere-turn method to test the current transformer for example: you need to test the 1000A / 5A transformer please pass the test wire of the instrument through the two turns of the current transformer and then test A current input is only 500A. This test method does not affect the validity of the transformer test data.
 
 Similarly other transformation ratios use the following processing methods:

Rated once (A)

Number of turns

Instrument primary current (A)

80

2

40

120

2

60

8000

2

4000

12000

2

6000


3) Working range of the tested current transformer: 1% ~ 200%
 
4) Secondary load: 2.5VA ~ 300VA COSφ = 0.1 ~ 1.0
 
5) Accuracy range of tested current transformer: 1.0 0.5 0.5S 0.2 and 0.2S
 
6) Resistance / admittance measurement error: ≤5.0%
 
7) Measuring range: R: 0.00Ω ~ 20.0Ω
 
              Y: 0.000mS ~ 100.0mS
 
2. Part of the voltage transformer calibrator
 
1) Basic error:
 
a. In-phase component:
 
2. Part of the voltage transformer calibrator
 
1) Basic error:
 
a. In-phase component: X = (X × 2% + Y × 2% 2 words)
 
     Y = (X × 2% + Y × 2% 5 words)
 
     "X" "Y"-display value of the instrument
 
     "5 words"-quantization error of the instrument
 
b. Percentage Table: Level 1
 
c. Measuring range: f: 0.0000% ~ 200.0%
 
             Δ: 0.000 ′ ~ 999.9 ′
 
3. Instrument power consumption: 20VA
 
4. Instrument accuracy level: 0.05S level
 
5. Maximum external dimension: 460 × 375 × 183mm
 
6. Weight: 10.0kg


 

Quality Keep Improving - Service Pursuing Perfection Pre-sales service commitment Provide professional consulting service; dedicated salesman and professional technical engineer to answer customer questions Ensure customer get the detailed information about the product in hand Reasonable price. Quotation stamped and confirmed by Manager

Welcome customers visit on-purchase service commitment The contract and the technical agreement to sign by both parties Being trustworthy, follow the requirements and ensure successful implementation of signed contracts and technical agreements Focus on communication, actively communicate with users, take notes of user’s questions and schedule, provide the necessary technical support. Move quick and efficient, professional on delivery, installation, debugging, training and others

After-sales service commitment Professional after-sales service department; ask and listen to customer’s feedback about the products and take records. Product guaranty: one year free warranty, life long maintenance, since the delivery of the product Provide solutions within 24 hours when there is problems feedback from customer. Professional research and development team.

Recommended products

Email:
whgdmk@yeah.net
Skype:
Emma Lei
live:.cid.d703d549beaabb3e
电话:
+8618164248846